Wilo-Stratos-D
|
|
Glandless double circulation pump with flange connection, EC motor with automatic power adjustment
Hot-water heating systems of all kinds, air-conditioning systems, closed cooling circuits, industrial circulating systems
|

Special features/Product advantages - Energy efficiency class A
- Maximum efficiency due to ECM technology
- Up to 80% electricity savings compared to uncontrolled circulation pumps
- Optimum handling due to front operation and front access to the terminal room, variable installation positions, position-independent display, combination flanges PN 6/PN 10 (for DN 32 to DN 65)
- Can be used in cooling/air-conditioning systems without ambient temperature limits
- Pump housing with cataphoretic (KTL) coating for the prevention of corrosion by condensation formation
- System extension due to retrofit communication modules LON, CAN, PLR, etc.
- Remote control via infrared interface (IR-Module/IR-Monitor)
- Integrable dual pump management due to retrofit Stratos IF-Modules:
- Main/standby mode with fault-dependent switchover
- Efficiency-optimised peak-load operation
- Main/standby mode with fault-dependent switchover
- Efficiency-optimised peak-load operation
Technical data - Permissible temperature range -10°C to +110°C
- Mains connection 1~230 V, 50/60 Hz
- Protection class IP 44
- Flange connection DN 32 to DN 80
- Max. operating pressure, standard version: 6/10 bar or 6 bar (special version: 16 bar)

Equipment Operating modes- Manual control mode (n=constant)
- Δp-c for constant differential pressure
- Δp-v for variable differential pressure
- Δp-T for temperature-controlled differential pressure (programmable via IR-Module, IR-Monitor, LON or CAN)
Manual functions- Setting of operating mode
- Setting of differential-pressure setpoint
- Setting of "Autopilot" (automatic setback operation)
- Pump ON/OFF setting
- Speed setting (manual control mode)
Automatic functions- Infinitely variable power adjustment according to the operating mode
- "Autopilot" automatic setback operation
- Deblocking function
- Soft start
- Full motor protection with integrated trip electronics
External control functions- "Overriding Off" control input (possible with Stratos IF-Modules)
- "Overriding Min" control input (possible with Stratos IF-Modules)
- "Analogue In 0 - 10 V" control input (remote speed adjustment) (possible with Stratos IF-Modules)
- "Analogue In 0 - 10 V" control input (remote setpoint adjustment) (possible with Stratos IF-Modules)
Signal and display functions- Individual / collective fault signal (potential-free NC contact) (programmable with the IR-Monitor)
- Collective fault signal (potential-free NC contact)
- Individual run signal (potential-free NO contact) (possible with Stratos IF-Modules)
- Fault signal light
- LC display for indication of pump data and fault codes
Data exchange- Infrared interface for wireless data exchange with IR-Module/IR-Monitor (see IR-Module/IR-Monitor function table)
- Serial digital PLR interface for connection to BA via Wilo interface converter or company-specific coupling module (possible with Stratos IF-Modules)
- Serial digital LON interface for connection to a LONWORKS network (possible with Stratos IF-Modules)
- Serial digital CAN interface for connection to a CAN bus system (possible with Stratos IF-Modules)
Dual pump management (double pump or 2 x single pump)- Main/standby mode (automatic fault-actuated switchover/time-dependent pump cycling): Various combinations possible with Stratos IF-Modules (accessory)
- Parallel operation (efficiency-optimised peak load cut-in and out): Various combinations possible with Stratos IF-Modules (accessory)
Equipment- Twin switch-over valve in pump housing
- Plug-in position for optional extension with Wilo-IF-Modules

Description/Design - Glandless circulation double pump with EC motor and integrated automatic power adjustment
- Red button technology and graphic display
- Motor protection with trip electronics
- Plug connection for functional extension with optional IF-Modules for building automation (BA)
- Impeller with three-dimensionally curved blades and plastic can made of carbon fibre composite material
Materials - Pump housing: Grey cast iron
- Shaft: Stainless steel
- Bearing: Carbon, metal impregnated
- Impeller: Plastic
Scope of delivery - Pump
- Including installation and operating instructions
- Including washers for flange screws (for nominal connection diameters DN 32 - DN 65)
Wilo-Stratos-D
| | | | | |
|---|
| Stratos-D 80/1-12 CAN PN 6 | DN 80 | PN 6 | 1~ 230 V | 1,3 kW | | Stratos-D 80/1-12 CAN PN 16 | DN 80 | PN 16 | 1~ 230 V | 1,3 kW | | Stratos-D 80/1-12 CAN PN 10 | DN 80 | PN 16 | 1~ 230 V | 1,3 kW | | Stratos-D 65/1-12 CAN PN 16 | DN 65 | PN 16 | 1~ 230 V | 0,65 kW | | Stratos-D 65/1-12 CAN PN 6/10 | DN 65 | PN 6/10 | 1~ 230 V | 0,65 kW | | Stratos-D 50/1-9 CAN PN 16 | DN 50 | PN 16 | 1~ 230 V | 0,35 kW | | Stratos-D 50/1-9 CAN PN 6/10 | DN 50 | PN 6/10 | 1~ 230 V | 0,35 kW | | Stratos-D 50/1-8 CAN PN 16 | DN 50 | PN 16 | 1~ 230 V | 0,2 kW | | Stratos-D 50/1-8 CAN PN 6/10 | DN 50 | PN 6/10 | 1~ 230 V | 0,2 kW | | Stratos-D 50/1-12 CAN PN 16 | DN 50 | PN 16 | 1~ 230 V | 0,5 kW | | Stratos-D 50/1-12 CAN PN 6/10 | DN 50 | PN 6/10 | 1~ 230 V | 0,5 kW | | Stratos-D 40/1-8 CAN PN 16 | DN 40 | PN 16 | 1~ 230 V | 0,2 kW | | Stratos-D 40/1-8 CAN PN 6/10 | DN 40 | PN 6/10 | 1~ 230 V | 0,2 kW | | Stratos-D 40/1-12 CAN PN 6/10 | DN 40 | PN 6/10 | 1~ 230 V | 0,423 kW | | Stratos-D 32/1-8 CAN PN 16 | DN 32 | PN 16 | 1~ 230 V | 0,2 kW | | Stratos-D 32/1-8 CAN PN 6/10 | DN 32 | PN 6/10 | 1~ 230 V | 0,2 kW | | Stratos-D 32/1-12 CAN PN 16 | DN 32 | PN 16 | 1~ 230 V | 0,2 kW | | Stratos-D 32/1-12 CAN PN 6/10 | DN 32 | PN 6/10 | 1~ 230 V | 0,2 kW |